BIZONE gas-powder fire-extinguishing module МГПП-11.5-СО2- 3.1-РХ-АВСЕ-У2
Submit requestDescription
This module is designed for volumetric fire suppression of the following fire classes: A: Combustion of solid materials; B: Combustion of liquid substances; C: Combustion of gaseous substances; combustion of energized electrical equipment.Read more
Specifications
Parameter name |
МГПП-11.5-СО2-3.1-РХ-АВСЕ-У2 |
Area protected |
A class: 90 m3 В class: 60 м3 |
Explosion protection marking* |
1Ex db IIB T4 Gb X |
All characteristics
- Description
- Технические характеристики
- Сопроводительные документы
- Выполненные проекты
This module is designed for volumetric fire suppression of the following fire classes: A: Combustion of solid materials; B: Combustion of liquid substances; C: Combustion of gaseous substances; combustion of energized electrical equipment. The module provides volumetric suppression of fires of A, B, C classes and fire of live electrical equipment in rooms with the following area: V = 60 m3 for В class fire, V= 90 m3 for А class fire.
Explosion protection marking: 1Ex db IIB T4 Gb X.
The module is not designed for extinguishment of burnt substances without air access, as well as metals, alloys and metal-organic compounds.
Specifications
Parameter name |
МГПП-11.5-СО2-3.1-РХ-АВСЕ-У2 |
Area protected |
A class: 90 m3 В class: 60 m3 |
Explosion protection marking* |
1Ex db IIB T4 Gb X |
Fire classes according to GOST 27331 |
А, В, С, Е |
Fire-fighting agent |
Gas-powder |
Operating temperature range |
-50 0С+50 0С |
Total weight of module, maximum |
36.5 kg |
Weight of applied Feniks АВС-70 dry chemical powder |
8 kg |
Weight of applied gas (liquid carbon dioxide), maximum |
3.1 kg |
Length of fire-extinguishing agent jet during module operation |
5-6 m |
Direct current required for module start-up (flare cartridge) |
0,5 А 6-24 В |
Safe circuit control current |
0.05 А within 5 min; 0.005 А with no time limit |
Module actuating speed, maximum |
1 sec |
Time of supply of fire-extinguishing agent, maximum |
15 sec |
Piping connections |
Up to 12 m with 3 90° bends |
Dimensions, width x depth x height |
310 х 210 х 750 mm |
Service life |
At least 20 years |
* Not a source of explosion initiation.
Data on the equipment range on the website is for reference. Please, indicate technical specifications for the manufacturer before ordering the equipment.